Search Results
Found 4 results
510(k) Data Aggregation
(108 days)
The intended use of the Electric Wheelchair (Robooter E80), Model name: BBR-E80-01 and BBR-E80-02 is to provide outdoor and indoor mobility to persons limited to a seated position that are capable of operating a powered wheelchair.
The Electric Wheelchair (Robooter E80), Models name: BBR-E80-01,BBR-E80-02, is an indoor/outdoor, battery- operated, 2-wheel drive (rear-wheel drive) powered wheelchair.
It consists of four modules: seat system, control system, braking system, and drive system. The user sits in the wheelchair seat and uses the control system.
The control pad positioned on the right armrest, user can turn the wheelchair on, control the speed, and direct the movement.
The braking system employs an electromagnetic brake, when release the controller rocker, the electromagnetic brakes will be actuated, and the electric wheelchair will stop in several seconds. Electromagnetic brake will not take effect immediately, it will take effect after the wheel rotates for 1/2 cycle.
The wheelchair is powered by a 24V DC,12Ah or 20Ah rechargeable lithium-ion battery charged by an offboard lithium-ion battery charger. The wheelchair is driven by two DC motors.
The Electric Wheelchair (Robooter E80), Models name: BBR-E80-01,BBR-E80-02, contains Bluetooth 4.1 BLE technology. The device can be controlled by the controller rocker or remote control by a smartphone app via Bluetooth 4.1 Low Energy (BLE) wireless communication interface. The smartphone app is used to drive the chair remotely. For safety, controller rocker control is priority over the remote control by design. The smartphone app can also view the battery's status, adjust the speed gear level and lock/unlock the unattended device.
The wheelchair can be folded/expanded manually. The Left and right handrails (joystick) can be interchange.
N/A
Ask a specific question about this device
(168 days)
The intended use of the Electric Wheelchair (Robooter E60), Models name: BBR-E60-01,BBR-E60-02, BBR-E60-03, BBR-E60-04,BBR-E60-05,BBR-E60-06,BBR-E60-07,BBR-E60-08, is to provide outdoor and indoor mobility to persons limited to a seated position that are capable of operating a powered wheelchair.
The Electric Wheelchair (Robooter E60), Models name: BBR-E60-01, BBR-E60-02, BBR-E60-03, BBR-E60-04, BBR-E60-05, BBR-E60-06, BBR-E60-07, BBR-E60-08, is an indoor/outdoor, batteryoperated, 2-wheel drive (rear-wheel drive) powered wheelchair.
It consists of four modules: seat system, control system, and drive system. The user sits in the wheelchair seat and uses the control system.
The control pad positioned on the right armrest, user can turn the wheelchair on, control the speed, and direct the movement.
The braking system employs an electromagnetic brake, when release the controller rocker, the electromagnetic brakes will be actuated, and the electric wheelchair will stop in several seconds.
Electromagnetic brake will not take effect immediately, it will take effect after the wheel rotates for 1/2 cycle.
The wheelchair is powered by a 24V DC,20Ah or 25Ah rechargeable lithium-ion battery charged by an offboard lithium-ion battery charger. The wheelchair is driven by two DC motors.
The Electric Wheelchair (Robooter E60), Models name: BBR-E60-01, BBR-E60-02, BBR-E60-03, BBR-E60-04, BBR-E60-05, BBR-E60-06, BBR-E60-07, BBR-E60-08, contains Bluetooth 4.1 BLE technology. The device can be controlled by the controller rocker or remote control by a smartphone app via Bluetooth 4.1 Low Energy (BLE) wireless communication interface. The smartphone app is used to drive the chair remotely. For safety, controller rocker control is priority over the remote control by design. The smartphone app can also view the battery's status, adjust the speed gear level and lock/unlock the unattended device.
The wheelchair can be controlled an optional Bluetooth remote controller (BBR-BLERC series)
The wheelchair can be folded/expanded manually. The Left and right handrails (joystick) can be interchange.
The provided documentation is a 510(k) summary for an Electric Wheelchair (Robooter E60). This type of submission focuses on demonstrating substantial equivalence to a legally marketed predicate device rather than providing extensive details on a comprehensive clinical study to define and meet specific acceptance criteria in the same way one might for a novel diagnostic or therapeutic device.
Based on the provided text, the "acceptance criteria" are primarily defined by compliance with a comprehensive set of ISO 7176 series standards for wheelchairs, along with other relevant ISO and ANSI standards. The "study" proving the device meets these criteria refers to the non-clinical testing performed against these standards.
Here's the breakdown of the requested information based on the document:
1. Table of Acceptance Criteria and Reported Device Performance
The acceptance criteria are essentially the requirements set forth by the listed ISO and ANSI standards. The reported device performance is that it met these standards. Since the document doesn't provide specific numerical performance values for each standard (e.g., exact braking distance for a specific test case, or specific stability angles beyond the general 9° dynamic stability), but rather states "test results meet its design specification" or "all test results meet the requirements," a direct comparative table with quantitative acceptance vs. performance for each test is not fully derivable. However, we can represent the overall compliance.
| Acceptance Criterion (Standard Requirement) | Reported Device Performance |
|---|---|
| Biocompatibility: Conforms to ISO 10993-5 (Cytotoxicity), ISO 10993-10 (Sensitization), ISO 10993-23 (Irritation) | All user directly contacting materials are compliant with ISO 10993-5, ISO 10993-10, and ISO 10993-23 requirements. |
| EMC: Conforms to ISO 7176-21 and IEC 60601-2-1 | The EMC performance results meet the requirements of ISO 7176-21. |
| Static Stability: Conforms to ISO 7176-1 | The static stability has been determined, and test results meet its design specification. |
| Dynamic Stability: Conforms to ISO 7176-2 (e.g., 9° stability) | The dynamic stability has been determined, and test results meet its design specification (9° for proposed and predicate). |
| Brakes Effectiveness: Conforms to ISO 7176-3 | The effectiveness of brakes has been determined, and test results meet its design specification. (Min braking distance: 120cm for subject vs. 200cm for predicate, both compliant with the standard). |
| Energy Consumption/Range: Conforms to ISO 7176-4 | The theoretical distance range has been determined, and test results meet its design specification. |
| Dimensions, Mass, Maneuvering: Conforms to ISO 7176-5 | The dimensions and mass have been determined after testing. |
| Speed, Acceleration, Deceleration: Conforms to ISO 7176-6 | The dimensions and mass have been determined after testing. (Max forward speed: 8km/h for subject vs. 10km/h for predicate, both compliant with the standard). |
| Seating & Wheel Dimensions: Conforms to ISO 7176-7 | The seating and wheel dimensions have been determined after testing. |
| Static, Impact, Fatigue Strengths: Conforms to ISO 7176-8 | All test results meet the requirements in Clause 4 of ISO 7176-8. |
| Climatic Tests: Conforms to ISO 7176-9 | The device could continue to function according to manufacturer's specification after being subjected to each of the tests specified in Clause 8 of ISO 7176-9. |
| Obstacle-Climbing Ability: Conforms to ISO 7176-10 | The obstacle-climbing ability has been determined. (Climbing Height: 50mm for both subject and predicate). |
| Test Dummies: Conforms to ISO 7176-11 | The test dummies used in the testing series meet the requirements of ISO 7176-11. |
| Coefficient of Friction of Test Surfaces: Conforms to ISO 7176-13 | The coefficient of friction of test surfaces has been determined for use in other 7176 series tests. |
| Power and Control Systems: Conforms to ISO 7176-14 | All test results meet the requirements in various clauses of ISO 7176-14. |
| Information Disclosure, Documentation, Labeling: Conforms to ISO 7176-15 | Information disclosure, documentation, and labeling of the device meet the requirements of ISO 7176-15. |
| Resistance to Ignition of Postural Support Devices: Conforms to ISO 16840-10 | The performance of resistance to ignition meets the requirements of ISO 16840-10. |
| Batteries and Chargers: Conforms to ISO 7176-25 | The performance of batteries and charger meets the Requirements in Clause 5 and 6 of ISO 7176-25. |
| Wireless Coexistence: Conforms to ANSI C63.27-2017 | The wheelchair conforms to ANSI C63.27-2017. |
| Software Verification & Validation | Validation testing of the priority of the on-board "controller rocker" (joystick) over the wireless remote controllers was conducted. |
2. Sample Sizes used for the Test Set and Data Provenance
The document does not specify sample sizes (e.g., number of devices tested) for the non-clinical tests. It refers to these as "non-clinical tests" and details the standards followed. The data provenance is implied to be from the manufacturer's testing facilities (Shanghai Bangbang Robotics Co., Ltd.) as part of their submission for market clearance. These are prospective tests conducted to demonstrate compliance. There is no mention of country of origin of the data in terms of patient data, as this is a non-clinical submission.
3. Number of Experts used to establish the Ground Truth for the Test Set and the Qualifications of those Experts
This information is not applicable and not provided. The "ground truth" for non-clinical performance standards is defined by the standards themselves (e.g., a specific static stability angle, braking distance, etc.). Compliance is assessed by accredited testing bodies or manufacturer's internal quality systems against these defined requirements. There are no "experts" in the context of clinical interpretation to establish ground truth in this non-clinical submission.
4. Adjudication Method for the Test Set
This is not applicable to non-clinical technical performance testing. Adjudication methods (like 2+1, 3+1) are typically used in clinical studies involving interpretation by multiple human readers (e.g., radiologists) to establish a consensus ground truth when individual reader opinions might differ.
5. If a Multi-Reader Multi-Case (MRMC) Comparative Effectiveness Study was done, If so, what was the effect size of how much human readers improve with AI vs without AI assistance
No such study was done or reported. This submission is for an electric wheelchair, a physical medical device, not an AI-powered diagnostic or interpretive tool that would involve human readers. The document explicitly states "No clinical study is included in this submission."
6. If a Standalone (i.e. algorithm only without human-in-the-loop performance) was done
This is not applicable. The device is an electric wheelchair, not an algorithm, and the testing focuses on its physical and electrical safety and performance characteristics.
7. The Type of Ground Truth Used
The "ground truth" for the non-clinical tests is the performance metrics and criteria defined within the referenced international standards (ISO 10993, ISO 7176 series, ANSI C63.27) and the device's design specifications. For example, for static stability, the ground truth is the minimum stability angle specified by ISO 7176-1. For braking, it's the effectiveness criteria of ISO 7176-3.
8. The Sample Size for the Training Set
This is not applicable. This is a physical medical device, not a machine learning model that requires a training set.
9. How the Ground Truth for the Training Set was Established
This is not applicable for the same reason as point 8.
Ask a specific question about this device
(127 days)
The intended use of the Electric Wheelchair (Robooter E40), Model name: BBR-E40-01 is to provide outdoor and indoor mobility to persons limited to a seated position that are capable of operating a powered wheelchair.
The Electric Wheelchair (Robooter E40), Model name: BBR-E40-01 is an indoor/outdoor, battery-operated, 2-wheel drive (rear-wheel drive) powered wheelchair. It consists of four modules: seat system, control system, braking system, and drive system. The user sits in the wheelchair seat and uses the control system. The control panel positioned on the right or left armrest allows the user to turn the wheelchair on, control the speed, and direct the movement. The braking system employs an electromagnetic brake. When the controller rocker is released, the electromagnetic brakes will be actuated, and the electric wheelchair will stop in several seconds. The electromagnetic brake will not take effect immediately, it will take effect after the wheel rotates for 1/2 cycle. The wheelchair is powered by a 24V DC, 20Ah rechargeable lithium-ion battery charged by an offboard lithium-ion battery charger. The wheelchair is driven by two DC motors. The Electric Wheelchair (Robooter E40), Model name: BBR-E40-01 contains Bluetooth 4.1 BLE technology. The device can be controller rocker or remote control by a smartphone app via Bluetooth 4.1 Low Energy (BLE) wireless communication interface. The smartphone app is used to drive the chair remotely. For safety, control is priority over the remote control by design. The smartphone app can also view the battery's status, adjust the speed gear level and lock/unlock the unattended device. The wheelchair can be folded/expanded manually. The Left and right handrails (joystick) can be interchange.
The provided text is a 510(k) Summary for an Electric Wheelchair (Robooter E40), Model: BBR-E40-01. It describes how the device compares to a predicate device and the performance testing conducted to demonstrate substantial equivalence. However, it does not involve an AI algorithm with specific acceptance criteria related to accuracy, sensitivity, or specificity. Therefore, many of the requested categories are not applicable.
Here's an analysis of the available information:
1. A table of acceptance criteria and the reported device performance
For a medical device like an electric wheelchair, the "acceptance criteria" are compliance with various safety and performance standards, primarily ISO 7176 series, rather than metrics like accuracy or sensitivity for an AI system. The device aims to meet these standards to demonstrate substantial equivalence to a predicate device.
| Acceptance Criterion (Standard Compliance) | Reported Device Performance (Compliance) |
|---|---|
| ISO 7176-1:2014 (Static stability) | Complies |
| ISO 7176-2:2017 (Dynamic stability) | Complies |
| ISO 7176-3:2012 (Effectiveness of brakes) | Complies |
| ISO 7176-4:2008 (Energy consumption/range) | Complies |
| ISO 7176-5:2008 (Dimensions, mass, maneuvering) | Complies |
| ISO 7176-6:2018 (Max speed, accel, decel) | Complies |
| ISO 7176-7:1998 (Seating & wheel dimensions) | Complies |
| ISO 7176-8:2014 (Static, impact, fatigue strengths) | Complies |
| ISO 7176-9:2009 (Climatic tests) | Complies |
| ISO 7176-10:2008 (Obstacle-climbing ability) | Complies |
| ISO 7176-11:2012 (Test dummies) | Used for testing |
| ISO 7176-13:1989 (Coefficient of friction) | Used for testing |
| ISO 7176-14:2008 (Power & control systems) | Complies |
| ISO 7176-15:1996 (Information disclosure) | Complies |
| ISO 7176-16:2012 (Resistance to ignition) | Complies |
| ISO 7176-22:2014 (Set-up procedures) | Used for testing |
| ISO 7176-25:2013 (Batteries & chargers) | Complies |
| ISO 7176-21:2009 (EMC) | Complies |
| ANSI C63.27-2017 (Wireless Coexistence) | Complies |
| ISO 10993-5:2009 (Cytotoxicity) | Complies |
| ISO 10993-10:2021 (Skin Sensitization) | Complies |
| ISO 10993-23:2021 (Irritation) | Complies |
2. Sample size used for the test set and the data provenance (e.g. country of origin of the data, retrospective or prospective)
The document does not specify a "test set" in the context of an AI algorithm or data. The performance testing is described as non-clinical testing to ensure compliance with relevant ISO standards. This typically involves testing of physical units of the device. Sample sizes for these types of engineering tests are not usually reported in the same way as for clinical trials or AI validation sets. Data provenance (country of origin, retrospective/prospective) is not applicable or provided.
3. Number of experts used to establish the ground truth for the test set and the qualifications of those experts (e.g. radiologist with 10 years of experience)
This is not applicable as there is no mention of a "test set" that requires expert-established ground truth. The acceptance is based on compliance with engineering and safety standards.
4. Adjudication method (e.g. 2+1, 3+1, none) for the test set
This is not applicable for the type of device and testing described.
5. If a multi reader multi case (MRMC) comparative effectiveness study was done, If so, what was the effect size of how much human readers improve with AI vs without AI assistance
This is not applicable since the device is an electric wheelchair, not an AI-powered diagnostic or assistive tool for human "readers" or clinicians.
6. If a standalone (i.e. algorithm only without human-in-the-loop performance) was done
This is not applicable as the device is an electric wheelchair, not an algorithm.
7. The type of ground truth used (expert consensus, pathology, outcomes data, etc)
The "ground truth" for this device's performance is adherence to the measurement and safety requirements specified in the various ISO and ANSI standards listed. For example, for static stability, the ground truth is simply whether the device maintained stability under the specified test conditions.
8. The sample size for the training set
This is not applicable as the device is a physical product, not an AI algorithm requiring a training set.
9. How the ground truth for the training set was established
This is not applicable.
Ask a specific question about this device
(128 days)
The intended use of the Electric Wheelchair (Model: BBR-LY-01-01) is to provide outdoor and indoor mobility to persons limited to a seated position that are capable of operating a powered wheelchair.
The Electric Wheelchair (Model: BBR-LY-01-01) is an indoor/outdoor, battery-operated, 2-wheel drive (rear-wheel drive) powered wheelchair. lt consists of four modules: seat system, control system, braking system, and drive system. The user sits in the wheelchair seat and uses the control system. The control pad positioned on the right armrest, user can turn the wheelchair on, control the speed, and direct the movement. The braking system employs an electromagnetic brake, when release the controller rocker, the electromagnetic brakes will be actuated, and the electric wheelchair will stop in several seconds. Electromagnetic brake will not take effect immediately, it will take effect after the wheel rotates for 1/2 cycle. The wheelchair is powered by a 24V DC,20Ah rechargeable lithium-ion battery charged by an offboard lithium-ion battery charger. The wheelchair is driven by two DC motors. The Electric Wheelchair (Model: BBR-LY-01-01) contains Bluetooth 4.1 BLE technology. The device can be controlled by the controller rocker or remote control by a smartphone app via Bluetooth 4.1 Low Energy (BLE) wireless communication interface. The smartphone app is used to drive the chair remotely. For safety, controller rocker control is priority over the remote control by design. The smartphone app can also view the battery's status, adjust the speed gear level and lock/unlock the unattended device. The wheelchair can be folded automatically.
This document describes the FDA's 510(k) clearance for the Shanghai BangBang Robotics Co., Ltd. Electric Wheelchair (Model: BBR-LY-01-01). As such, it focuses on demonstrating "substantial equivalence" to a predicate device rather than providing a detailed study of the device's performance against specific acceptance criteria in the manner an AI/ML algorithm submission would.
Therefore, many of the requested points are not applicable to this type of regulatory submission for a physical medical device. However, I can extract the relevant information regarding performance and testing.
1. A table of acceptance criteria and the reported device performance
For a physical device like an electric wheelchair, "acceptance criteria" are generally compliance with recognized consensus standards. The performance is reported as meeting these standards.
| Acceptance Criterion (Standard Compliance) | Reported Device Performance (Compliance) |
|---|---|
| Static Stability (ISO 7176-1:2014) | Complies |
| Dynamic Stability (ISO 7176-2:2017) | Complies (specifically tested 6° dynamic stability vs. predicate's 10°) |
| Effectiveness of Brakes (ISO 7176-3:2017) | Complies (minimum braking distance 120cm vs. predicate's 1500mm) |
| Energy Consumption & Theoretical Distance Range (ISO 7176-4:2008) | Complies (driving range 20.6km vs. predicate's 17.7km) |
| Overall Dimensions, Mass, and Maneuvering Space (ISO 7176-5:2008) | Complies (dimensions differ from predicate but meet standard) |
| Maximum Speed, Acceleration, and Deceleration (ISO 7176-6:2018) | Complies (max forward speed 6km/h vs. predicate's 8km/h) |
| Measurement of Seating and Wheel Dimensions (ISO 7176-7:1998) | Complies (seating/wheel dimensions differ from predicate but meet standard) |
| Static, Impact, and Fatigue Strengths (ISO 7176-8:2014) | Complies |
| Climatic Tests (ISO 7176-9:2009) | Complies (operating/storage conditions differ from predicate but meet standard) |
| Obstacle-Climbing Ability (ISO 7176-10:2008) | Complies |
| Test dummies (ISO 7176-11:2012) | Complies |
| Determination of coefficient of friction of test surfaces (ISO 7176-13:1989) | Complies |
| Power and Control Systems (ISO 7176-14:2008) | Complies |
| Information Disclosure, Documentation and Labeling (ISO 7176-15:1996) | Complies |
| Resistance to Ignition of Postural Support Devices (ISO 7176-16:2012) | Complies |
| Set-up Procedures (ISO 7176-22:2014) | Complies |
| Batteries and Chargers (ISO 7176-25:2013) | Complies |
| Electromagnetic Compatibility (ISO 7176-21:2009 & IEC 60601-1-2:2014) | Complies |
| FCC RF Compliance (FCC CFR TITLE 47 PART 15 SUBPART C, PART 2.1093) | Complies (wireless RF frequency/output power differ from predicate but meet standard) |
| Wireless Coexistence (ANSI C63.27-2017) | Complies |
| Biocompatibility (ISO 10993-5:2009 & ISO 10993-10:2010) | Complies |
2. Sample sized used for the test set and the data provenance (e.g. country of origin of the data, retrospective or prospective)
This information is typically not included in a 510(k) summary for a non-software medical device. Testing against ISO standards usually involves a representative number of physical units, not a "test set" of data in the AI/ML sense. The testing would have been done by the manufacturer (Shanghai BangBang Robotics Co., Ltd. in China) and verified by a recognized testing body.
3. Number of experts used to establish the ground truth for the test set and the qualifications of those experts (e.g. radiologist with 10 years of experience)
Not Applicable. For a physical device, "ground truth" is established by the direct physical measurement and performance testing against the specifications outlined in the international consensus standards (e.g., measuring stability, braking distance, dimensions). This does not involve expert consensus in the diagnostic sense.
4. Adjudication method (e.g. 2+1, 3+1, none) for the test set
Not Applicable. Adjudication methods like 2+1 or 3+1 are used for establishing ground truth in image interpretation or similar diagnostic tasks, typically for AI/ML algorithms. This is not relevant for the performance testing of an electric wheelchair.
5. If a multi reader multi case (MRMC) comparative effectiveness study was done, If so, what was the effect size of how much human readers improve with AI vs without AI assistance
Not Applicable. MRMC studies are specific to evaluating the impact of AI on human readers (e.g., radiologists interpreting images). This device is a physical product (electric wheelchair) and does not involve "human readers" or "AI assistance" in that context.
6. If a standalone (i.e. algorithm only without human-in-the-loop performance) was done
Not Applicable. This device is an electric wheelchair, not an algorithm. While it has a control system and Bluetooth connectivity, its primary function is mechanical mobility, and it is always operated with a human in the loop (the user or a remote controller).
7. The type of ground truth used (expert consensus, pathology, outcomes data, etc)
The "ground truth" for this device's performance is compliance with international consensus standards (ISO 7176 series and others) through objective performance testing and measurement. For example, the braking distance being 120cm is a factual measurement, not an expert opinion or pathology finding.
8. The sample size for the training set
Not Applicable. This is not an AI/ML algorithm, so there is no "training set."
9. How the ground truth for the training set was established
Not Applicable. No training set exists for this type of device submission.
Ask a specific question about this device
Page 1 of 1